E-AY2Y - PVC Insulated Heavy Current Cable (Aluminum Conductor, PE Sheathed)
E-AY2Y PVC Insulated Heavy Current Cable (Aluminum Conductor, PE Sheathed)
Product Descriptions
Application
For fixed installations; preferably in cable ducts in open space, suitable for underwater or underground use (when mechanical damage is not expected).
Structure
- Solid (RESE) or stranded (RMSM) aluminum conductor
- Core insulation Polyvinylchloride (PVC)
- Core sheathing or banding PVC
- Outer cover Black, Shore hardness HD 55-60, UV resistant polyethylene (PE)
Short Circuit Information
- Short Circuit Operating Temperature (max. 5 s) 160 °C
- Short Circuit Time (max.) 5 s
Standards
- ÖVE K 23 - ÖVE K 603 - HD 603 S1 - DIN EN 60228 Class 1 and 2 - HD 308 S2 (conductor color coding)
Technical Data
- Nominal Voltage U₀U [V] 600 1000
- Test Voltage [V] AC 4000
Temperature Range
- Movable -5 °C ... +70 °C
- Constant -20 °C ... +70 °C
Bending Radius (according to diameter)
- Single conductor 15 × diameter
- Multiconductor 12 × diameter
Flame Resistance Standard EN 60332-1-2
Core × Cross Section (mm²) | Aluminum (kg/km) | Ø (mm) | Weight (kg/km) | Current in Earth [A] | Current in Air [A] |
---|---|---|---|---|---|
1×120 RM | 348 | 20 | 525 | 389 | 302 |
3×240/120 SM | 2 470 | 55 | 3 994 | 364 | 338 |
4×25 RE | 294 | 24 | 769 | 102 | 82 |
4×50 SE | 588 | 28 | 1 093 | 144 | 119 |
4×95 SE | 1 117 | 37 | 1 930 | 215 | 186 |
4×150 SE | 1 764 | 45 | 2 822 | 275 | 246 |
4×25 RM | 294 | 24 | 769 | 102 | 82 |
4×35 SM | 412 | 25 | 868 | 123 | 100 |
4×50 SM | 588 | 28 | 1 091 | 144 | 119 |
4×95 SM | 1 117 | 37 | 1 930 | 215 | 186 |
4×150 SM | 1 764 | 43 | 2 449 | 275 | 246 |
4×185 SM | 2 176 | 48 | 3 075 | 313 | 285 |
4×240 SM | 2 822 | 57 | 4 509 | 364 | 338 |