E-AYY - PVC Insulated Cable (Aluminum Conductor)
E-AYY PVC Insulated Cable (Aluminum Conductor)
Product Descriptions
Application
- For fixed installations; preferably in cable ducts, indoor, outdoor, underwater or underground use (when mechanical damage is not expected).
Structure
- Solid (SE) or stranded (RMSM) aluminum conductor
- Core insulation Polyvinylchloride (PVC)
- Core sheathing or banding PVC
- Outer cover Black, UV resistant PVC
Short Circuit Information (in core, max. 5 s)
- ≤ 300 mm² → 160 °C
- 300 mm² → 140 °C
Standards
- ÖVE K 23 - ÖVE K 603 - HD 603 S11994 + A22003 - DIN EN 60228 Class 1 and 2 - HD 308 S2 (conductor color coding)
Technical Data
- Nominal Voltage U₀U [V] 600 1000
- Test Voltage [V] AC 4000
Temperature Range
- Movable -5 °C ... +70 °C
- Constant -20 °C ... +70 °C
Bending Radius (according to diameter)
- Single conductor 15 × diameter
- Multiconductor 12 × diameter
Flame Resistance Standard EN 60332-1-2
Core × Cross Section (mm²) | Aluminum (kg/km) | Ø (mm) | Weight (kg/km) | Current (On Earth) [A] | Current (In Air) [A] |
---|---|---|---|---|---|
1 × RM 25 | 74 | 11 | 174 | 106 | 87 |
1 × RM 35 | 103 | 12 | 209 | 127 | 107 |
1 × RM 50 | 147 | 14 | 282 | 151 | 131 |
1 × RM 70 | 206 | 16 | 363 | 185 | 166 |
1 × RM 95 | 279 | 18 | 520 | 222 | 205 |
1 × 120 RM | 353 | 19 | 557 | 253 | 239 |
1 × RM 150 | 441 | 21 | 674 | 284 | 273 |
1 × RM 185 | 544 | 24 | 826 | 322 | 317 |
1 × 240 RM | 706 | 26 | 1 052 | 375 | 378 |
1 × RM 300 | 882 | 29 | 1 282 | 425 | 437 |