FG7OR - Power Cable

Untitled-1

FG7OR - Power Cable

FG7OR Power Cable

Insulated with high quality EPM rubber, PVC sheathed; prevents the spread of fire and ensures low corrosive gas emission.

Product Descriptions

Implementation:

For fixed installations; preferably in cable ducts, indoors, outdoors, underwater or underground (when mechanical damage is not expected).

Structure:

  1. Fine stranded copper conductor, class 5
  2. Hard EPM rubber insulation
  3. Thermoplastic filling compound - fire resistant, water-repellent
  4. Abrasion-resistant PVC outer jacket - fire resistant, low water permeability

Short Circuit Resistance (max. 5 s):

  • ≤ 250 mm² → 250 °C
  • 250 mm² → 220 °C

Standards

  • CEI 20-13 - IEC 60502-1 - CEI UNEL 35375 (1-5 conductor) - CEI UNEL 35377 (6+ conductor)

Technical Data

  • Nominal Voltage U₀/U \[V]: 600 / 1000
  • Test Voltage \[V] AC: 4000

Temperature Range:

  • Movable: 0 °C ... +90 °C
  • Constant: -15 °C ... +90 °C

Bending Radius (relative to diameter):

  • Power cable: 4 × diameter
  • Signal cables: 6 × diameter

Flame Resistance Standard: EN 60332-1-2

Core × Cross Section (mm²) Copper (kg/km) Ø (mm) Weight (kg/km) Current (On Earth) [A] Current (In Air) [A]
1×1,5 14,4 5,8 47 21 24
1×2,5 24 6,3 60 27 33
1×4 38,4 6,7 78 35 45
1×6 57,6 7,4 103 44 58
1×10 96 8,3 146 59 80
1×16 153,7 9,5 204 77 107
1×25 241 11,0 300 100 135
1×35 336 12,0 399 121 169
1×50 480 14,0 550 150 207
1×70 672 16,1 781 184 268
1×95 912 18,0 1010 217 328
1×120 1155 19,0 1263 251 383

Contact us for more information about our products and to request tailor-made cable and raw material solutions for your needs.