FG7OR - Power Cable
FG7OR Power Cable
Insulated with high quality EPM rubber, PVC sheathed; prevents the spread of fire and ensures low corrosive gas emission.
Product Descriptions
Implementation:
For fixed installations; preferably in cable ducts, indoors, outdoors, underwater or underground (when mechanical damage is not expected).
Structure:
- Fine stranded copper conductor, class 5
- Hard EPM rubber insulation
- Thermoplastic filling compound - fire resistant, water-repellent
- Abrasion-resistant PVC outer jacket - fire resistant, low water permeability
Short Circuit Resistance (max. 5 s):
- ≤ 250 mm² → 250 °C
- 250 mm² → 220 °C
Standards
- CEI 20-13 - IEC 60502-1 - CEI UNEL 35375 (1-5 conductor) - CEI UNEL 35377 (6+ conductor)
Technical Data
- Nominal Voltage U₀/U \[V]: 600 / 1000
- Test Voltage \[V] AC: 4000
Temperature Range:
- Movable: 0 °C ... +90 °C
- Constant: -15 °C ... +90 °C
Bending Radius (relative to diameter):
- Power cable: 4 × diameter
- Signal cables: 6 × diameter
Flame Resistance Standard: EN 60332-1-2
Core × Cross Section (mm²) | Copper (kg/km) | Ø (mm) | Weight (kg/km) | Current (On Earth) [A] | Current (In Air) [A] |
---|---|---|---|---|---|
1×1,5 | 14,4 | 5,8 | 47 | 21 | 24 |
1×2,5 | 24 | 6,3 | 60 | 27 | 33 |
1×4 | 38,4 | 6,7 | 78 | 35 | 45 |
1×6 | 57,6 | 7,4 | 103 | 44 | 58 |
1×10 | 96 | 8,3 | 146 | 59 | 80 |
1×16 | 153,7 | 9,5 | 204 | 77 | 107 |
1×25 | 241 | 11,0 | 300 | 100 | 135 |
1×35 | 336 | 12,0 | 399 | 121 | 169 |
1×50 | 480 | 14,0 | 550 | 150 | 207 |
1×70 | 672 | 16,1 | 781 | 184 | 268 |
1×95 | 912 | 18,0 | 1010 | 217 | 328 |
1×120 | 1155 | 19,0 | 1263 | 251 | 383 |