PROFIBUS-DP
PROFIBUS-DP
Application Areas
In SCADA systems, communication between the host computer and devices such as sensors, motors, thermocouples and automatic valves over a single line
- Water and natural gas distribution networks
- Electricity generation and distribution facilities
- Fuel filling facilities
- Power plants
- Production lines
Cable Structure
- Conductor Electrolytic copper, Ø 0.64 mm (22 AWG)
- Insulation Foamed polyethylene (Foamed PE)
- Insulation Colors:
- A wire Green
- B wire Red
- Individual Screen PES tape + Al-PES foil
- Genel Ekran: Kalaylı bakır tel örgü (min. %85 kapama)
- Outer Sheath: PVC compound, color: RAL 4001 (purple)
Technical Data
Feature Value
- Loop Resistance [Ω/km] 110
- Insulation Resistance [MΩ-km] ≥ 1000 (500 V)
- Operating Voltage [V] 300
- Test Voltage (vessel/vessel) [V] 1200 AC
- Bending Radius (min.) 12 × cabel outer diameter
- Characteristic Impedance [Ω] 150 ± 15 %
- Effective Capacity [nF/km] 30
- Operating Temperature -40 °C ... +70 °C
- Flame Retardancy Test IEC 60332-1-2 - VDE 0482-332-1-2 - EN 60332-1-2
Transmission Performance
Data Rate [kbit/s] Max. Line Length [m]
- 9,6 1200
- 93,75 1200
- 187,5 1000
- 500 400
- 1200 200
- 12000 100
Attenuation
Frequency Attenuation [dB/km]
- 9.6 kHz 2.5
- 38.4 kHz 4
- 4 MHz 22
- 16 MHz 22