N2XSY - XLPE Insulated Single Core Cable (6/10 kV, 12/20 kV, 18/30 kV)
N2XSY | XLPE Insulated Single Core Cable (6/10 kV, 12/20 kV, 18/30 kV)
Product Descriptions
It is designed for installation directly into the ground, indoors and outdoors and in cable ducts.
Structure
- Stranded (RM) bare copper conductor
- Inner semiconductor layer
- Core insulation: Cross-linked polyethylene (XLPE)
- Outer semiconductor layer
- Screen: Copper wires
- Outer cover Red PVC
Standards
- DIN VDE 0276-620 - HD 620 S1:1995 - DIN EN 60228 Class 2
Technical Data
Test Voltage [kV] / Duration:
- 6/10 kV → 21 kV/5 min
- 12 / 20 kV → 42 kV / 5 min
- 18/30 kV → 63 kV/5 min
Temperature Range:
- Movable: -5 °C ... +70 °C
- Constant: -20 °C ... +70 °C
- Short Circuit Operating Temperature: 250 °C
- Short Circuit Time (max.): 5 s
- Bend Radius (min., diameter ×): 15
- Flame Resistance Standard: EN 60332-1-2
6/10 kV | ||||||
---|---|---|---|---|---|---|
Cross section (mm²) | Copper (kg/km) | Ø aprox. (mm) | Ø max. (mm) | Weight (kg/km) | Current (On Earth) [A] | Current (In Air) [A] |
1×35 RM/16 | 518,40 | 23 | 28 | 900 | 187 | 197 |
1×50 RM/16 | 662,40 | 24 | 29 | 1050 | 220 | 236 |
1×70 RM/16 | 854,40 | 26 | 31 | 1300 | 268 | 294 |
1×95 RM/16 | 1094,40 | 27 | 32 | 1600 | 320 | 358 |
1×120 RM/16 | 1334,40 | 29 | 34 | 1850 | 363 | 413 |
1×150 RM/25 | 1723,20 | 30 | 35 | 2200 | 405 | 468 |
1×185 RM/25 | 2059,20 | 32 | 37 | 2600 | 456 | 535 |
1×240 RM/25 | 2587,20 | 34 | 39 | 3150 | 526 | 631 |
1×300 RM/25 | 3163,20 | 36 | 40 | 3750 | 591 | 722 |
1×400 RM/35 | 4233,60 | 40 | 45 | 4650 | 662 | 827 |
1×500 RM/35 | 5193,60 | 43 | 47 | 5750 | 739 | 921 |
12/20 kV | ||||||
---|---|---|---|---|---|---|
Cross section (mm²) | Copper (kg/km) | Ø aprox. (mm) | Ø max. (mm) | Weight (kg/km) | Current in Ground (A) | Current In Air (A) |
1×35 RM/16 | 518,40 | 27 | 32 | 1 100 | 189 | 200 |
1×50 RM/16 | 662,40 | 28 | 33 | 1 250 | 222 | 239 |
1×70 RM/16 | 854,40 | 30 | 35 | 1 450 | 271 | 297 |
1×95 RM/16 | 1 094,40 | 31 | 36 | 1 750 | 323 | 361 |
1×120 RM/16 | 1 334,40 | 33 | 38 | 2 050 | 367 | 416 |
1×150 RM/25 | 1 723,20 | 34 | 39 | 2 400 | 409 | 470 |
1×185 RM/25 | 2 059,20 | 36 | 41 | 2 800 | 461 | 538 |
1×240 RM/25 | 2 587,20 | 39 | 44 | 3 400 | 532 | 634 |
1×300 RM/25 | 3 163,20 | 41 | 46 | 4 000 | 599 | 724 |
1×400 RM/35 | 4 233,60 | 44 | 49 | 4 950 | 671 | 829 |
1×500 RM/35 | 5 193,60 | 47 | 52 | 6 050 | 754 | 953 |
18/30 kV | ||||||
---|---|---|---|---|---|---|
Cross section (mm²) | Copper (kg/km) | Ø aprox. (mm) | Ø max. (mm) | Weight (kg/km) | Current in Ground (A) | Current In Air (A) |
1×50 RM/16 | 662,40 | 33 | 38 | 1450 | 225 | 241 |
1×70 RM/16 | 854,40 | 35 | 40 | 1700 | 274 | 299 |
1×95 RM/16 | 1094,40 | 36 | 41 | 2050 | 327 | 363 |
1×120 RM/16 | 1334,40 | 38 | 43 | 2300 | 371 | 418 |
1×150 RM/25 | 1723,20 | 39 | 44 | 2700 | 414 | 472 |
1×185 RM/25 | 2059,20 | 41 | 46 | 3100 | 466 | 539 |
1×240 RM/25 | 2587,20 | 43 | 48 | 3700 | 539 | 635 |
1×300 RM/25 | 3163,20 | 46 | 51 | 4350 | 606 | 725 |
1×400 RM/35 | 4233,60 | 49 | 54 | 5300 | 680 | 831 |
1×500 RM/35 | 5193,60 | 52 | 57 | 6450 | 765 | 953 |