(N)YM(ST)-J - Screened PVC Sheathed Fixed Installation Cable
(N)YM(ST)-J | Screened PVC Sheathed Fixed Installation Cable
Application Areas
- Dry, damp and wet indoor fixed installations,
- In environments requiring effective electromagnetic interference suppression,
- Not suitable for embedding in concrete or laying in the open,
- It should not be used in areas where there is a risk of explosion.
Cable Structure
- Conductor Class 1, single core bare copper
- Insulation Polyvinylchloride (PVC)
- Screen Plastic coated aluminum foil + tinned earth wire
- Outer Case: Gray PVC
Standards
- DIN VDE 0250-204
- DIN EN 60228 Class 1 (conductor structure)
- HD 308 S2 (vessel identification)
Technical Data
Feature Value
- Rated Voltage U₀/U [V] 300 / 500
- Test Voltage [V AC] 2000
- Temperature Range (Moving) +5 °C ... +70 °C
- Short Circuit Operating Temperature [°C] 160
- Short Circuit Time (max.) [s] 5
- Bend Radius 4 × cable outer diameter
- Flame Retardancy Standard EN 60332-1-2
Number of Cores and Cross Section (mm²) | Copper Quantity (kg/km) | Conductor Structure (approximate value, mm) | Outer Diameter (mm) | Calorific Potential (kWh/m) | Weight (kg/km) |
3 × 1,5 / 1,5 | 52,80 | 1 × 1,38 | 10,5 | 0,44 | 140 |
4 × 1,5 / 1,5 | 65,28 | 1 × 1,38 | 11,5 | 0,53 | 188 |
5 × 1,5 / 1,5 | 79,68 | 1 × 1,38 | 12,0 | 0,58 | 216 |
7 × 1,5 / 1,5 | 108,48 | 1 × 1,38 | 13,0 | 0,67 | 263 |
3 × 2,5 / 1,5 | 79,68 | 1 × 1,78 | 12,0 | 0,58 | 214 |
5 × 2,5 / 1,5 | 127,68 | 1 × 1,78 | 13,5 | 0,75 | 300 |