Contact us
Follow Us

Nord Group

We offer the widest range of products and services to all our local and global customers

Contact

Address
Merkez Mahallesi Hasat Sokak Kamara Plaza No:52/1 Sisli / Istanbul / Turkey
Telephone
+90 212 963 13 38
+90 212 963 13 41
Email
info@nordgroup.com.tr
Page title icon

Solar PLUS DB H1Z2Z2-K - Halogen Free Crosslinked Polyolefin (XLPO) DC Power Cable

Solar PLUS DB H1Z2Z2-K

Solar PLUS DB H1Z2Z2-K - Halogen Free Crosslinked Polyolefin (XLPO) DC Power Cable

H1Z2Z2-K | Halogen Free Crosslinked Polyolefin (XLPO) DC Power Cable

Features You Will Benefit From

  • Certification: EN 50618; New Norm: IEC 62930
  • Nominal Voltage: 1.5 kV DC (max. operating voltage 1.8 kV DC; additional internal review for 2.0 kV DC)
  • Direct Burial Approval: UL 44 cl. 5.4 & UL 2566 cl. 6.4.4.4.2 high quality material
  • CPR Flame Behavior: Dca (EN 50575)
  • Short Circuit Resistance: 250 °C / 5 s
  • Reinforced Cable Covering:
  • Impact resistant (UL 854.23)
  • Crush resistant (UL 854.24) - internal review

UV Stability:

  • 720 saat sonra gerilme dayanıklılığı ve maksimum uzama (360 devir) ≥ ilk değerlerin %70’i
  • Measurement: EN 50289-4-17, Method A; EN ISO 4892-1 (2000) & EN ISO 4892-2 (2006)
  • Easy Installation: Shipped with meter marker

Structure

  • Fine stranded copper conductor
  • Core isolation: XLPO cross-linked with electron-beam
  • Outer sheath: Electron-beam cross-linked XLPO

Standards

  • Europe: EN 50618, IEC 62930, EN 50575 (CPR Dca
  • US Recessed Approval: UL 44 cl. 5.4, UL 2566 cl. 6.4.4.2
  • Impact / Crush Resistance: UL 854.23 / UL 854.24
  • UV Tests: EN 50289-4-17, EN ISO 4892-1, EN ISO 4892-2

Technical Data

  • Nominal Voltage [DC]: 1 500 V
  • Operating Voltage [DC]: 1 800 V (2 000 V subject to additional review)
  • Short Circuit Resistance: 250 °C / 5 s
  • UV Stabilite: ≥ %70 dayanıklılık (720 saat, 360 devir)
  • Reel Length: 500 m (standard, including meter marker)
Cross-sectional area (mm²) Conductor Construction n × max-Ø (mm) Maximum resistance of conductor (Ω/km) Cable outer diameter (± 0.2 mm) Copper (kg/km) Weight ~ (kg/km)
1 × 2,5 50 × 0.26 8.21 5.0 24.0 45.0
1 × 4,0 56 × 0.31 5.09 5.4 38.4 55.0
1 × 6,0 80 × 0.31 3.39 6.0 57.6 75.0
1 × 10,0 80 × 0.41 1.95 7.1 96.0 115.0
1 × 16,0 120 × 0.41 1.24 8.1 153.6 170.0
1 × 25,0 196 × 0.41 0.795 10.3 240.0 270.0
1 × 35,0 280 × 0.41 0.565 11.8 336.0 370.0

Contact us for more information about our products and to request tailor-made cable and raw material solutions for your needs.