Page title icon

J-Y(ST)Y - Telecommunication Installation Cable

Untitled-1 copy

J-Y(ST)Y - Telecommunication Installation Cable

J-Y(St)Y | Telecommunication Installation Cable

Application Areas

  • Signal transmission for telecommunication purposes in indoor fixed installations
  • Telephone exchanges, data lines and similar low speed communication applications

Cable Structure

  • Conductor Ø 0.6 mm or Ø 0.8 mm single core bare copper
  • Insulation Polyvinylchloride (PVC)
  • Static Screen Plastic coated aluminum foil + tinned earth wire
  • Outer Case: Gray PVC

Information

Conductor Loop Resistance:

  • Ø 0.6 mm → 130 Ω/km
  • Ø 0.8 mm → 73.2 Ω/km

Standards

  • Core Identification: DIN VDE 0815
  • Conductor Construction: DIN EN 60228 Class 1
  • Flame Retardancy: EN 60332-1-2 & EN 60332-2-2

Technical Data

Feature Value

  • Peak Operating Voltage [V] 300
  • Test Voltage (vein/vessel) [V AC] 800
  • Test Voltage (vessel/display) [V AC] 800
  • Temperature Range Moving: -5 °C ... +50 °C<br/>Constant: -30 °C ... +70 °C
  • Bend Radius 15 × cable outer diameter
  • Insulation Resistance (min.) [MΩ/km] 100
  • Mutual Capacitance (max.) [nF/km] 10
  • Capacity Unbalance (100 m) [pF] 300
For conductor Ø 0.6 mm
Number of Pairs and Nominal Wire Diameter (mm) Copper Quantity (kg/km) Insulation Thickness (mm) Outside Diameter (approx. mm) Weight (approx. kg/km)
1 × 2 × 0,6 6,72 1,1 4,5 26
2 × 2 × 0,6 12,48 1,1 4,9 35
3 × 2 × 0,6 18,24 1,1 6,2 49
4 × 2 × 0,6 23,04 1,1 6,6 58
5 × 2 × 0,6 28,80 1,1 7,1 59
6 × 2 × 0,6 34,56 1,1 7,6 61
10 × 2 × 0,6 56,64 1,1 9,3 113
12 × 2 × 0,6 69,12 1,1 9,5 129
20 × 2 × 0,6 111,36 1,1 10,9 191
30 × 2 × 0,6 165,12 1,3 13,7 284
40 × 2 × 0,6 218,88 1,3 14,5 358
50 × 2 × 0,6 273,60 1,3 16,5 438
60 × 2 × 0,6 328,32 1,3 17,5 512
100 × 2 × 0,6 545,28 1,5 22,1 829
For conductor Ø 0.8 mm
Number of Pairs and Nominal Wire Diameter (mm) Copper Quantity (kg/km) Insulation Thickness (mm) Outside Diameter (approx. mm) Weight (approx. kg/km)
1 × 2 × 0,8 10,56 1,1 5,5 38
2 × 2 × 0,8 20,16 1,1 6,1 54
3 × 2 × 0,8 29,76 1,1 8,0 77
4 × 2 × 0,8 39,36 1,1 8,7 94
5 × 2 × 0,8 49,92 1,1 9,4 114
6 × 2 × 0,8 59,52 1,1 10,1 135
10 × 2 × 0,8 98,88 1,3 13,1 205
12 × 2 × 0,8 118,08 1,3 13,5 235
16 × 2 × 0,8 157,44 1,3 14,8 299
20 × 2 × 0,8 194,88 1,3 15,6 352
30 × 2 × 0,8 291,84 1,5 19,4 522
40 × 2 × 0,8 387,84 1,5 20,9 663
50 × 2 × 0,8 484,80 1,7 23,7 832
60 × 2 × 0,8 581,76 1,7 25,8 978

Contact us for more information about our products and to request tailor-made cable and raw material solutions for your needs.