YXC8VZ2V-R - 26/45-47 kV XLPE Insulated
26/45-47 kV XLPE Insulated, Three Core, Round Steel Wire Armored, Copper Conductor Cable
Product Descriptions
Implementation:
These cables are used in outdoor, cable ducts, indoor and underground applications for power supply of residential and industrial areas where short circuit currents are high. Ideal for areas with mechanical stress.
Structure
- Stranded copper conductor
- Inner semiconductor layer
- Core insulation: Cross-linked polyethylene (XLPE)
- Outer semiconductor layer
- Semiconductor tape
- Copper screen
- Filling
- Intermediate sheath
- Galvanized round steel wire armor
- Galvanized steel tape
- Outer sheath: PVC
Standards
- TS IEC 60502-2 - VDE 0276
Technical Data
- Maximum operating temperature: 90 °C
- Maximum short-circuit temperature (≤ 5 s): 250 °C
- Minimum operating temperature: -20 °C
Technical Specifications / Technical Features | ||||||||
---|---|---|---|---|---|---|---|---|
Normal Section Rated Cross Section |
Cable Outer Diameter Overall Diameter Of Cable |
Current Carrying Capacity Current Carrying Capacity |
Operating Inductance Operating Inductance |
Operation Capacity Operating Capacity |
Conductor DC Resistance (20 ºC) Conductor DC Resistance at (20 ºC) |
Net Weight Net Weight |
Shipment Length Delivery Length |
|
mm² | mm | Air in Air (A) | Ground on Earth (A) | mH / Km | µF/km | Ohm / Km | Kg / Km | Mt |
3×50/16 | 95.30 | 215 | 214 | 0,468 | 0,098 | 0,3870 | 15 230 | 200 |
3×70/16 | 98.90 | 267 | 264 | 0,442 | 0,108 | 0,2680 | 16 600 | 200 |
3×95/16 | 103.40 | 325 | 315 | 0,418 | 0,119 | 0,1930 | 18 390 | 200 |
3×120/16 | 107.20 | 375 | 360 | 0,403 | 0,128 | 0,1530 | 20 000 | 200 |
3×150/25 | 110.50 | 424 | 403 | 0,390 | 0,137 | 0,1240 | 21 680 | 200 |
3×185/25 | 114.70 | 486 | 455 | 0,375 | 0,148 | 0,0991 | 23 730 | 200 |
3×240/25 | 120.30 | 453 | 529 | 0,360 | 0,162 | 0,0754 | 26 710 | 200 |
3×300/25 | 125.90 | 651 | 593 | 0,346 | 0,176 | 0,0601 | 29 850 | 200 |