Aer (Alpek)
AER (Alpek) Cable
Product Descriptions
Suspension stranded, bundled aluminum conductor aerial line cable offers advantages in installation costs and safe use and is widely preferred in low and medium voltage distribution lines.
Black PE or XLPE insulation, wrapped around an alloy aluminum suspension wire, provides high resistance to external conditions and mechanical loads.
Suitable for use in in-settlement energy distribution lines.
Structure
- Conductor Pure aluminum
- Insulation PE or XLPE
- Hanger Wire Alloy aluminum carrier wire
Technical Data
- Rated Voltage U₀/U: 0.6 / 1 kV
- Test Voltage 3.5 kV AC
- Operating Temperature: PE: +70 °C, XLPE: +90 °C
- Short Circuit Temperature (≤5 s): PE: 160 °C, XLPE: 250 °C
- Bend Radius: 12 × cable outer diameter
- Flame Spread Test: EN 60332-1-2
Advantages
- Insulated phase conductors reduce the risk of electrical failure and maintenance costs.
- Offers high breakdown voltage and low insulation failure rate compared to bare conductors.
Nominal Cross Section (mm²) | Hanger Rope Diameter (mm) | Conductor Diameter (mm) | Conductor Resistance Max. (Ω/km @ 20 °C) | Carrier Rope Resistance Max. (Ω/km @ 20 °C) | Approximate Net Weight (kg/km) |
---|---|---|---|---|---|
1×16+25 | 5,9 | 4,5 | 1,91 | 1,38 | 140 |
1×25+35 | 6,9 | 6,2 | 1,20 | 0,986 | 200 |
1×35+50 | 8,1 | 7,1 | 0,868 | 0,72 | 280 |
1×16+1×16+25 | 5,9 | 4,5 | 1,91 | 1,38 | 210 |
3×16+25 | 5,9 | 4,5 | 1,91 | 1,38 | 280 |
3×25+35 | 6,9 | 6,3 | 1,20 | 0,986 | 400 |
3×35+50 | 8,1 | 7,2 | 0,868 | 0,72 | 560 |
3×50+70 | 9,7 | 8,1 | 0,641 | 0,493 | 730 |
3×70+95 | 11,4 | 9,8 | 0,443 | 0,363 | 1030 |
3×120+95 | 11,0 | 12,6 | 0,253 | 0,363 | 1150 |
3×16+1×16+25 | 5,9 | 4,5 | 1,91 | 1,38 | 350 |
3×25+1×16+35 | 6,9 | 6,3 | 1,20/1,91 | 0,986 | 480 |
3×35+1×16+50 | 8,1 | 7,2 | 0,868/1,91 | 0,72 | 630 |
3×50+1×16+70 | 9,7 | 7,1 | 0,641/1,91 | 0,493 | 800 |
3×70+1×16+95 | 11,4 | 9,8 | 0,443/1,91 | 0,363 | 1100 |
4×16+25 | 5,9 | 4,5 | 1,91 | 1,38 | 350 |
4×25+35 | 6,9 | 6,1 | 1,20 | 0,986 | 510 |