E-Y2Y - PVC Insulated Heavy Current Cable (Copper Conductor, PE Sheathed)
E-Y2Y | PVC Insulated Heavy Current Cable (Copper Conductor, PE Sheathed)
Product Descriptions
Implementation:
For fixed installations; preferably in cable ducts, indoor, outdoor, underwater or underground use (when mechanical damage is not expected).
Structure
- Solid (RE) or stranded (RM/SM) bare copper conductor
- Core insulation: Polyvinylchloride (PVC)
- Core sheathing or taping: PVC
- Outer cover: Black, Shore-hardness > 55, UV-resistant polyethylene (PE)
Short Circuit Information (max. 5 s)
- ≤ 300 mm² → 160 °C
- 300 mm² → 140 °C
Standards
- ÖVE K 23 - ÖVE K 603 - HD 603 S1:1994 + A2:2003 - DIN EN 60228 Class 1 and 2 - HD 308 S2 (conductor color coding)
Technical Data
- Nominal Voltage U₀/U \[V]: 600 / 1000
- Test Voltage \[V] AC: 4000
Temperature Range:
- Movable: -5 °C ... +70 °C
- Constant: -20 °C ... +70 °C
- Short Circuit Operating Temperature: 160 °C
- Short Circuit Time (max.): 5 s
Bending Radius (relative to diameter):
- Single conductor 15 × diameter
- Multiconductor 12 × diameter
Flame Resistance Standard: EN 60332-1-2
Core × Cross Section (mm²) | Copper (kg/km) | Ø (mm) | Weight (kg/km) | Current in Earth [A] | Current in Air [A] |
---|---|---|---|---|---|
4×6 RE | 230,40 | 15 | 570 | 56 | 43 |
4×10 RE | 384,00 | 20 | 775 | 75 | 60 |
4×10 RM | 384,00 | 20 | 775 | 75 | 60 |
4×16 RE | 614,40 | 21 | 1 100 | 98 | 80 |
4×16 RM | 614,40 | 22 | 1 100 | 98 | 80 |
4×25 RM | 960,00 | 25 | 1 632 | 128 | 106 |
4×35 SM | 1 344,00 | 27 | 1 959 | 157 | 131 |
4×50 SM | 1 920,00 | 32 | 2 595 | 185 | 159 |
5×6 RE | 288,00 | 17 | 672 | * | * |
5×10 RE | 480,00 | 21 | 921 | * | * |