J-H(ST)H...Bd - Halogen Free Telecommunication Cable
J-H(ST)H...Bd | Halogen Free Telecommunication Cable
Product Descriptions
Implementation:
For fixed installations in telecommunication systems; used in fire risk environments to minimize damage during fire.
Structure
- Solid bare copper conductor
- Core isolation: Halogen-free polymer (HI 2)
- Foil layer
- Static screen: Plastic coated aluminum foil and drainage wire
- Outer sheath: Halogen-free polymer (HM 2), grey color, flame retardant
Information
The conductors are twisted in a star-quad pattern; each unit has 5 quads, the units are placed in layers. Layers are marked with colored bands.
Standards
- DIN VDE 0815 (conductor color coding) - DIN EN 60228 Class 1 (construction) - DIN VDE 0207-24
Technical Data
- Peak Operating Voltage [V]: 300
- Temperature Range:
- Movable: -5 °C ... +50 °C
- Constant: -30 °C ... +70 °C
- Bending Radius (moving, relative to diameter): 7.5 × diameter
- Flame Resistance Standard: EN 50266-2-4 - IEC 60332-3 Cat. C
Cross Section Table
Number of Pairs × Diameter (mm) | Copper (kg/km) | Insulation Thickness (mm) | Outside Diameter (approx. mm) | Calorific Potential (kWh/m) | Weight (kg/km) |
---|---|---|---|---|---|
2 × 2 × 0,6 | 12,48 | 1,0 | 6,0 | 0,17 | 49 |
4 × 2 × 0,6 | 23,04 | 1,0 | 8,6 | 0,29 | 82 |
6 × 2 × 0,6 | 34,56 | 1,0 | 9,0 | 0,34 | 99 |
10 × 2 × 0,6 | 56,64 | 1,0 | 10,4 | 0,44 | 135 |
20 × 2 × 0,6 | 111,36 | 1,0 | 12,8 | 0,69 | 223 |
30 × 2 × 0,6 | 165,12 | 1,0 | 14,9 | 0,92 | 306 |
40 × 2 × 0,6 | 218,88 | 1,0 | 16,7 | 1,14 | 386 |
50 × 2 × 0,6 | 273,60 | 1,4 | 18,7 | 1,45 | 485 |