JE-H(ST)H BMK...Bd E30 - Halogen Free and Flame Retardant Fire Detection Circuit Cable
JE-H(ST)H BMK ...Bd E30 | Halogen Free and Flame Retardant Fire Detection Circuit Cable (30 min Circuit Integrity, 180 min Insulation Integrity)
Product Descriptions
Implementation:
It is used in fire detection circuits for fixed installations; in fire risk environments, in projects requiring at least 180 minutes of isolation and 30 minutes of circuit integrity.
Information:
These cables meet the test requirements of 180 min insulation integrity according to DIN VDE 0472-814/8.83 and 30 min circuit integrity according to IEC Publ. 331 (1970) and DIN 4102-12 (VDE 0100-710/718) and 30 min circuit integrity test requirements.
Structure:
- Solid bare copper conductor
- Core insulation: Halogen-free, ceramic-like polymer compound (HI 1), twisted
- Plastic foil sheet
- Static screen Plastic coated aluminum foil + 0.8 mm tinned drainage wire
- Outer sheath: Halogen-free polymer (HM 2), red, printed "BRANDMELDEKABEL"
Standards
- DIN VDE 0815 - DIN EN 60228 Class 1 - DIN VDE 0207-24
Technical Data
- Peak Operating Voltage [V]: 225
- Temperature Range:
- Movable: - 5 °C ... + 50 °C
- Constant: - 30 °C ... + 70 °C
- Bending Radius (moving, relative to diameter): 7.5 × diameter
- Flame Resistance Standard: EN 50266-2-4 - EN 60332-1 - IEC 60332-3 Cat. C
- Insulation Resistance (min. [MΩ-km]): 100
- Mutual Capacity: Max. [nF/km]: 120
- Capacity Unbalance 100 m (max. [pF]): 200
Number of Cores and Nominal Diameter (mm) | Copper Quantity (kg/km) | Insulation Thickness (mm) | Outer Diameter (mm) | Calorific Potential (kWh/m) | Weight (kg/km) |
---|---|---|---|---|---|
2 × 2 × 0,8 | 24,00 | 1,0 | 6,6 | 0,13 | 61 |
4 × 2 × 0,8 | 43,20 | 1,0 | 8,8 | 0,20 | 104 |
8 × 2 × 0,8 | 81,60 | 1,2 | 12,8 | 0,34 | 218 |
12 × 2 × 0,8 | 120,96 | 1,2 | 13,5 | 0,39 | 235 |
20 × 2 × 0,8 | 197,76 | 1,4 | 16,1 | 0,53 | 367 |