JE-H(ST)H BMK...Bd E90

Untitled-1

JE-H(ST)H BMK...Bd E90

JE-H(ST)H BMK ...Bd E90 | Halogen Free and Flame Retardant Industrial Electronic Installation Cable (90 min Circuit Integrity, 180 min Insulation Integrity)

Product Descriptions

Implementation:

For fixed installations in telecommunication and industrial electronic installations; used in fire risk environments, in projects requiring at least 180 minutes of insulation integrity and 90 minutes of circuit integrity.

Information:

These cables meet the test requirements of 180 min insulation integrity according to DIN VDE 0472-814/8.83 and 90 min circuit integrity according to IEC Publ. 331 and DIN 4102-12 (VDE 0100-710/718) and 90 min circuit integrity test requirements.

Structure

  • Solid bare copper conductor
  • Core sheath wrapped with glass fiber (MICA) tape
  • Core isolation: Halogen-free, cross-linked polymer
  • Conductors are divided into binary and quad star-quad groups
  • Groups are identified by a helical "Z" mark or a ring mark on the insulation
  • Plastic foil sheet
  • Static screen Plastic laminated aluminum foil + 0.8 mm tinned drainage wire
  • Outer sheath: Halogen-free polymer (HM 2), red, printed "BRANDMELDEKABEL"

Standards

  • DIN VDE 0815 (conductor color coding) - DIN EN 60228 Class 1 - DIN VDE 0207-24

Technical Data

  • Peak Operating Voltage [V]: 225
  • Temperature Range:
  • Movable: -5 °C ... +50 °C
  • Constant: -30 °C ... +70 °C
  • Bending Radius (moving, relative to diameter): 7.5 × diameter
  • Flame Resistance Standard: EN 50266-2-4 - EN 60332-1 - IEC 60332-3 Cat. C
  • Insulation Resistance (min. [MΩ-km]): 100
  • Mutual Capacity [Ω/km]: 73,2
  • Capacity (max. [nF/km]): 120
  • Capacity Unbalance 100 m (max. [pF]): 200
Number of Cores and Nominal Diameter (mm) Copper Quantity (kg/km) Insulation Thickness (mm) Outer Diameter (mm) Calorific Potential (kWh/m) Weight (kg/km)
2 × 2 × 0,8 24,00 1,0 12,8 0,56 177
4 × 2 × 0,8 43,20 1,0 16,3 0,85 284
8 × 2 × 0,8 81,60 1,2 20,3 1,33 447
12 × 2 × 0,8 120,96 1,2 23,9 1,84 615
16 × 2 × 0,8 159,36 1,4 26,6 2,22 756
20 × 2 × 0,8 197,76 1,4 29,4 2,72 921

Contact us for more information about our products and to request tailor-made cable and raw material solutions for your needs.