N2XS(F)2Y - Longitudinally Waterproof PE Sheathed Single Core XLPE Insulated Cable (6/10 kV, 12/20 kV, 18/30 kV)
N2XS(F)2Y | Longitudinally Waterproof PE Sheathed Single Core XLPE Insulated Cable (6/10 kV, 12/20 kV, 18/30 kV)
Product Descriptions
Suitable for direct laying in soil, water, indoor and outdoor areas and cable ducts.
Structure
- Stranded (RM) bare copper conductor
- Inner semiconductor layer
- Core insulation: Cross-linked polyethylene (XLPE)
- Outer semiconductor layer
- Swellable tape
- Screen: Copper wires
- Longitudinal waterproofing tape
- Outer sheath: Black polyethylene (PE)
Standards
- DIN VDE 0276-620 - HD 620 S1:1995 - DIN EN 60228 Class 2
Technical Data
Test Voltage / Duration:
- 6/10 kV → 21 kV/5 min
- 12 / 20 kV → 42 kV / 5 min
- 18/30 kV → 63 kV/5 min
Temperature Range:
- Movable: -20 °C ... +90 °C
- Constant: -20 °C ... +90 °C
- Short Circuit Operating Temperature: 250 °C
- Short Circuit Time (max.): 5 s
- Bend Radius (min., diameter ×): 15
- Flame Resistance Standard: EN 60332-1-2
6/10 kV | ||||||
---|---|---|---|---|---|---|
Cross section (mm²) | Copper (kg/km) | Ø aprox. (mm) | Ø max. (mm) | Weight (kg/km) | Earth Current (A) | Air Flow (A) |
1×35 RM/16 | 518,40 | 23 | 28 | 820 | 187 | 197 |
1×50 RM/16 | 662,40 | 24 | 29 | 960 | 220 | 236 |
1×70 RM/16 | 854,40 | 26 | 31 | 1 200 | 268 | 294 |
1×95 RM/16 | 1 094,40 | 27 | 32 | 1 450 | 320 | 358 |
1×120 RM/16 | 1 334,40 | 29 | 34 | 1 700 | 363 | 413 |
1×150 RM/25 | 1 723,20 | 30 | 35 | 2 000 | 405 | 468 |
1×185 RM/25 | 2 059,20 | 32 | 37 | 2 350 | 456 | 535 |
1×240 RM/25 | 2 587,20 | 34 | 39 | 2 900 | 526 | 631 |
1×300 RM/25 | 3 163,20 | 36 | 41 | 3 550 | 591 | 722 |
1×400 RM/35 | 4 233,60 | 40 | 45 | 4 500 | 662 | 827 |
1×500 RM/35 | 5 193,60 | 43 | 48 | 5 550 | 744 | 949 |