(N)2XY - PVC Insulated 0.6/1 kV Single and Multi-Core Heavy Current Cable
N)2XY | PVC Insulated 0.6/1 kV Single and Multi-Core Heavy Current Cable
Product Descriptions
Implementation:
For fixed installations; preferably in cable ducts, indoors, outdoors, underwater or underground (when mechanical damage is not expected).
Structure:
- Solid (RE) or stranded (RM/SM) bare copper conductor
- Core insulation: Polyvinylchloride (PVC)
- Core sheathing or taping: PVC
- Outer sheath: Black, Shore hardness > 55, polyethylene (PE)
Standards
DIN VDE 0276-603 - DIN EN 60228 Class 1 and 2 - HD 308 S2 (conductor color coding)
Technical Data
- Nominal Voltage U₀/U \[V]: 600 / 1000
- Test Voltage \[V] AC: 4000
Temperature Range:
- Movable: -5 °C ... +70 °C
- Constant: -20 °C ... +70 °C
Bending Radius (relative to diameter):
- Single core 15 × diameter
- Multi-core 12 × diameter
Flame Resistance Standard: EN 60332-1-2
Number of cores × Cross section (mm²) | Copper (kg/km) | Ø (mm) | Weight (kg/km) | Earth Current (A) | Air Flow (A) |
---|---|---|---|---|---|
4×1.5 RE | 57,60 | 11,3 | 189 | 31 | 24 |
4×2.5 RE | 96,00 | 12,3 | 243 | 40 | 32 |
4×4 RE | 153,60 | 13,4 | 314 | 52 | 42 |
4×6 RM | 230,40 | 14,6 | 408 | 64 | 53 |
4×10 RM | 384,00 | 17,9 | 655 | 86 | 74 |
4×16 RM | 614,40 | 20,5 | 944 | 112 | 98 |
4×25 RM | 960,00 | 24,2 | 1 397 | 145 | 133 |
4×35 SM | 1 344,00 | 26,9 | 1 806 | 174 | 162 |
4×50 SM | 1 920,00 | 30,2 | 2 369 | 206 | 197 |
4×70 SM | 2 688,00 | 35,4 | 3 365 | 254 | 250 |
4×95 SM | 3 648,00 | 40,9 | 4 586 | 305 | 308 |
4×120 SM | 4 608,00 | 44,2 | 5 516 | 348 | 359 |
4×150 SM | 5 760,00 | 49,0 | 6 940 | 392 | 412 |
4×185 SM | 7 104,00 | 55,8 | 8 645 | 444 | 475 |
4×240 SM | 9 216,00 | 62,7 | 11 126 | 517 | 564 |
4×300 SM | 11 520,00 | 68,4 | 13 688 | 585 | 649 |